Matrix Installation and Operation Instructions
9.2.2 Setting Matrix Fan Control
Just as the Matrix Boiler Controller controls all of the operation and safety functions of the boiler, the Matrix Fan Controller,
controls all of the operation and safety functions related to air ha ndling a nd hot water dispatching. The fa n controller controls the
forced air modulation, ventilation, as well as priority of domestic hot water and secondary heating systems.
Menu Level Description
Main Sub Value
RUN
When Run is displayed, controller is in ‘Prog’ mode. Arrow up or down to
scroll through menus
OFF HRV Mode – Always off unless call for high ventilation (DH)
HRV
ON
HRV Mode – Continuous Ventilation. HRV will exchange air at low
ventilation rate during a call for forced air heat (W1 or W2) or continuous
circulation (G). Will increase to high ventilation rate with a high
ventilation call (24vac @ DH)
PF1 Heat Profile 1 300/800 cfm 66,000 Btu/h max.
PF2 Heat Profile 2 400/1000 cfm 83,000 Btu/h max.
HEA
PF3 Heat Profile 3 500/1200 cfm 92,000 Btu/h max.
COO 40-160 Cooling Flow *10 = CFM (400-1600) cfm
SCL 30-100
ECL 30-100
SCH 30-100
ECH 30-100
SOL 30-100
EOL 30-100
SOH 30-100
BAL
EOH 30-100
HRV Balancing – (see HRV section for more details)
H2O 100-160 Sets DHW Target Temperature, recommend 120-130ºF
Table 9.5 Matrix Fan Control Programming
To start the control operation, you must return to RUN on the menu, and press Function. Norma
operation will begin. Controller will return to RUN mode if no button is pressed for 2 minutes.
Menu Level Description
Main Value Typical Settings
RUN
Program Mode - When Run is displayed controller
is in ‘Prog’ mode. Arrow up or down to scroll
through menus
H2O 80-190 DHW Setpoint 160
HYD 80-200 Hydronic Call Setpoint
100-120 Infloor (High Mass)
140-160 Infloor (Low Mass)
140-160 Fan Coil
HI 80-200
Auxiliary Heat Setpoint – prior to outdoor reset
adjustment
190
DIF 1-40
Differential Setting - Applies only to Hydronic Only
setpoint. Temperature difference below setpoint at
which burner will re-light.
10
RES 70-190
Sets Outdoor Reset Curve Slope – See
Determining Reset Temperature for more
information.
85
SFS 75-100 Starting Gas Input Value 80
HFS 100-240 Maximum Gas Input Value 240
LFS 46-100 Minimum Gas Input Value 48 (min 46)
FrE ON/OFF
Freeze Protection – Operates burner and circulator
if temperature drops below 40ºF.
ON
Sto OFF-24
Storage Feature Timer – Length of time in hours
storage feature will keep boiler hot.
4
Table 9.4 Matrix Boiler Control Programming
To start the control operation, you must return to RUN on the menu, and press Function. Norma
operation will begin. Controller will return to RUN mode if no button is pressed for 2 minutes.